Sensitivity Analysis of Per-Query Water Estimates

This lesson is built with resources from youtube.com, cacm.acm.org and 1 more site.

Hello. The previous lesson showed why a facility’s annual water total cannot, by itself, establish local water pressure: the source, season, and return location matter. A per-query figure adds another layer of interpretation. It assigns some portion of a data center’s water consumption to one request, even though cooling and electricity serve many requests and other workloads.

This lesson tests how that figure changes when you vary two assumptions: the electricity used by a request and the share of facility water assigned to the service handling it. Allow about 40 minutes, including the resource study.


A per-query figure is an allocation

The diagram separates water consumed onsite for cooling from water associated with generating the electricity a facility uses. It shows pathways, not measured water volumes for individual requests.

The onsite cooling tower represents direct water consumption; cooling associated with electricity generation represents indirect consumption. Neither pathway has an inherent “liters per query” until energy and shared water use are allocated to queries.

A useful starting model assigns water to a request according to its server electricity:

Here is the request’s IT or server electricity in kilowatt-hours; is onsite water consumption per kilowatt-hour of IT electricity; is power usage effectiveness, or PUE; and is electricity-generation water consumption per kilowatt-hour of facility electricity. Thus estimates the facility electricity assigned to the request. Both water terms must measure consumption, not withdrawals, if their sum is to represent consumption.

Read the operational model in Making AI Less ‘Thirsty’ before using its numerical example.

Making AI Less ‘Thirsty’

Read the article’s operational-water formula to see how server energy, onsite water intensity, PUE, and electricity-related water intensity fit together.

Find the bold paragraph beginning “Operational water footprint,” immediately before “Embodied water footprint.” Read the operational model and the equation that completes that paragraph. Focus on which energy quantity multiplies the onsite term and why PUE multiplies the offsite term. The following embodied-water paragraph is outside this lesson’s calculations.

The model is an average attribution, not a meter reading taken while one request runs. If onsite water usage effectiveness was calculated from all onsite consumption divided by IT electricity, its intensity already assigns shared cooling water across IT activity. Adding a second allowance for that same water would double count it. Similarly, PUE accounts for electricity overhead; it is not a multiplier to apply again to an onsite intensity already expressed per IT kilowatt-hour.

The units provide a quick check. Kilowatt-hours per request multiplied by liters per kilowatt-hour yields liters per request. PUE has no units. A result in liters becomes milliliters by multiplying by .



Test the workload-energy assumption

The article supplies a per-request energy assumption and a table of estimated results. Its inference discussion also describes why a different request or computing system might require more energy. Treat those values as scenario inputs, not as measurements of every query.

Making AI Less ‘Thirsty’

Continue with the article’s case study and inference discussion. They show how an assumed server-energy figure enters a per-request estimate and how the estimated result varies across facilities.

In “Case Study: Estimating GPT-3’s operational water consumption footprint,” read the case setup, then inspect the “U.S. Average” row of Table 1, “Estimate of GPT-3’s operational water consumption footprint.” In the bold “Inference” subsection, read the request assumption. Continue from the energy comparison. Note the request size and the difference between an assumed energy value and a universally measured one.

Using the case study’s U.S.-average illustrative inputs— kilowatt-hours per request, onsite intensity liters per IT kilowatt-hour, PUE , and offsite intensity liters per facility kilowatt-hour—the estimate is:

Of this estimate, milliliters are assigned onsite and about milliliters offsite. Those components can affect different water systems; their sum does not describe pressure on one local basin.

Now hold the water intensities and PUE fixed while using kilowatt-hours per request as a higher-energy scenario. Since this model multiplies both terms by , four times the assumed energy produces four times the estimate: approximately milliliters per request. That is a sensitivity result, not a claim that every request on the case-study system uses the higher energy value. If request length, hardware, utilization, or time of operation changes, the other inputs may change too.



Test the shared-water allocation

An intensity such as onsite water usage effectiveness hides an allocation rule: facility consumption is spread over IT electricity. To examine that choice explicitly, use a different, hypothetical facility model. Do not add the following shared-water pool to the article’s onsite intensity; this example replaces that onsite calculation with separate components.

Suppose a facility reports liters of onsite water consumption in one month that cannot be attributed directly to individual requests. It hosts several services. The service under study handles requests that month, and the remaining assumptions are:

  • Its workload-dependent onsite consumption is liters per IT kilowatt-hour.
  • PUE is , and the applicable grid-consumption factor is liters per facility kilowatt-hour.
  • A fraction of the -liter shared pool is assigned to this service. The rest is assigned to other services.

The service’s per-request estimate is:

The first term is in liters per request; the second divides the service’s assigned share of monthly onsite consumption among its monthly requests. For kilowatt-hours and , the workload-dependent onsite and offsite terms total milliliters. The allocated shared pool contributes another milliliters, giving milliliters per request. These numbers are invented solely to expose the assumptions.

A fraction of needs a defensible basis, such as the service’s share of IT electricity over the same month. A share based instead on occupied server-hours could differ. Neither rule identifies water molecules used by a particular request; each apportions a measured total. The request count must cover the same period and service as the allocated water. If other workloads are present, assigning the entire pool to this service would overstate its share.

The following video illustrates why the definition of a request and the allocation of earlier, shared activity also matter. Use its discussion of allocation choices rather than treating its provider-specific speculation as measured evidence.

Why is Everyone So Wrong About AI Water Use??

Watch selected passages from Hank Green’s “Why is Everyone So Wrong About AI Water Use??” for examples of how a user-facing request and an allocated footprint can be defined differently.

Watch request definitions for the distinction between a user interaction and processing behind it. Then watch allocation choices for alternative ways to spread training-related water across later use. Focus on the choice of numerator and denominator, not on unverified claims about a particular service.

Training water illustrates a separate accounting boundary. An inference-only estimate excludes it. A broader operational footprint could report training water separately and assign a share across an expected number of lifetime requests. For example, allocating a hypothetical -liter training footprint over one million requests assigns milliliters to each; over ten million requests, it assigns milliliters. The training total has not changed—only the denominator has. Such an allocation must not be described as water newly consumed whenever a request arrives.



Read a two-assumption sensitivity table

Return to the hypothetical monthly facility model. Vary request energy and the share of its shared onsite pool assigned to the service, keeping request count and all other inputs fixed. Each cell reports milliliters of operational water consumption per request.

IT electricity per request
kWh 13.2 mL 18.2 mL 23.2 mL
kWh 21.4 mL 26.4 mL 31.4 mL
kWh 37.8 mL 42.8 mL 47.8 mL

At the middle allocation share, raising assumed energy from to kilowatt-hours changes the result from to milliliters. It does not quadruple the total: the -milliliter shared allocation per request remains fixed in this scenario. At the lowest energy assumption, changing from to moves the result from to milliliters without changing the water measured for the facility.

That last distinction is central. Sensitivity to an assumption is not evidence that the facility’s physical water consumption changed. The share changes attribution among services. Changing request energy would change modeled workload-related consumption, but holding PUE, the grid factor, and the monthly shared pool constant is only an approximation. Sustained changes in workload or utilization could alter those quantities as well.

For a credible published estimate, keep alongside the headline number its request definition, energy measurement or estimate, request count and period, rule for assigning shared water, onsite and offsite factors, and inclusion or exclusion of training. An apparent disagreement between per-query numbers may disappear—or become much more informative—once those choices are visible.



Key takeaways

Per-query water consumption is an accounting estimate with a defined boundary. Under a fixed-intensity model, the result scales directly with assumed request energy. When a fixed facility-water pool is allocated across requests, changing energy affects only part of the total, while changing the allocation rule can change the reported figure without changing measured facility use. Onsite and electricity-related components also need to remain identifiable because their water sources and local impacts differ.