Welcome back. In the previous lesson, you divided onsite water consumption by IT equipment electricity to calculate a consumption-based WUE. This lesson keeps those two measurements distinct while introducing a third: total facility electricity. You will use power usage effectiveness (PUE) to calculate it, then identify why it—not just IT electricity—is the relevant electricity quantity when estimating water consumed to generate the facility’s power. Allow about 40 minutes, including the short video and readings.
What PUE measures
Servers, storage, and networking equipment use electricity, but so do the systems that support them: cooling equipment, pumps, lighting, and electrical distribution. PUE compares the energy entering the data-center boundary with the energy used by its IT equipment.
Watch this short explanation before working with the formula.
Fundamentals of Data Center Power: Power Calculations
Watch “Fundamentals of Data Center Power: Power Calculations” from GogoTraining for its distinction between IT load and supporting electrical loads.
Watch the PUE definition, then the load breakdown. Focus on which equipment draws electricity, rather than treating the speaker’s illustrative proportions as values for every facility.
For an all-electric facility, using electricity measured over one common period:
Both energies must use the same unit, such as kilowatt-hours (kWh), and cover the same facility and period. PUE is dimensionless: kWh divided by kWh. A PUE of means the facility used kWh of electricity for every kWh used by IT equipment. The additional kWh covers supporting loads and losses; it is not electricity used by the IT equipment itself.
The measurement period matters. An annual electricity-related water estimate needs annual electricity, not a single reading of power in kilowatts (kW). A PUE calculated from a snapshot of power may describe that moment, but it need not equal the ratio of energy used across the year.
The following reading gives the formal definition and explains the preference for annual energy measurements.
Measuring PUE for Data Centers - eere.energy.gov
Read Section 3 of “Measuring PUE for Data Centers” for its definition of PUE and its measurement-period guidance.
On p. 4, in “3 PUE Metric Calculation,” begin where the text recommends annual energy consumption. Read the PUE definition through the paragraph introducing boundary considerations. Notice that the definition permits power readings, but recommends annual energy consumption for reporting.
Recover total facility electricity from IT electricity
Rearranging the PUE definition gives the calculation needed here:
You can also isolate the electricity used outside the IT equipment:
Consider the illustrative annual facility from the previous lesson. Its IT equipment used , and its total facility electricity was . Those measurements imply a PUE of . If instead you were given the IT electricity and PUE, you could recover the facility total:
The difference, , is supporting electricity, including any cooling and power-delivery loads inside the specified boundary. Do not multiply the IT electricity by PUE and then add IT electricity again: the facility total already includes it.
The diagram below shows the same accounting with another set of numbers.

In the PUE: A Simple Example diagram, the supporting amounts add to . Together with for IT, they account for all of facility energy shown. The boxes allocate energy, not water: a chiller’s is electricity use, not a volume of water consumed. For unit consistency, is .
Which electricity belongs in a water calculation?
The denominator of the onsite WUE from the previous lesson remains IT electricity. Electricity-related water accounting asks a different question: how much water was consumed offsite to generate the electricity serving the facility? That electricity serves both IT equipment and supporting systems. For an all-electric facility, the energy quantity to pair with an appropriately defined electricity-generation water factor is therefore , not .
For the illustrative facility above, that means starting with , not . Using only IT electricity would omit generation associated with the facility’s of supporting electricity. It would not change the onsite WUE denominator; the two calculations have different purposes.
The Green Grid’s source-based water discussion makes this link between PUE and facility energy explicit. Its historical water-intensity figures are not factors to apply indiscriminately to a present-day site; the factor’s location, time, and definition will matter in the next lesson.
[PDF] WATER USAGE EFFECTIVENESS (WUE™) - The Green Grid
Revisit The Green Grid’s discussion of site-based and source-based water use to see why the latter needs the facility’s total energy.
In Section III, “Water Usage Effectiveness (WUE),” on pp. 6–7, start at the paragraph distinguishing the two metrics. Read the source discussion, ending after the explanation of local values. Focus on the sentence beginning “To determine the source energy water usage”: it specifies why total facility energy must be known.
There is one important boundary qualification. The multiplication yields total energy under the reported PUE definition. It yields purchased facility electricity only when that total is electricity. If a site also purchases district chilled water or uses another energy input, a PUE that includes those inputs cannot be multiplied by IT electricity and treated automatically as the site’s electricity-meter reading. For an electricity-generation water calculation, obtain the electricity portion separately and check how any onsite generation is accounted for.
The contrasting examples in this reading make that distinction concrete.
Measuring PUE for Data Centers - eere.energy.gov
Read the paired examples in Appendix A to see how the inputs behind a PUE can differ, even when the reported PUEs are similar.
On p. 12, under “Appendix A. Example PUE Calculation Using Source Energy Weighting Factors,” find the paragraph introducing Case A and Case B. Read the paired cases. Compare the listed electricity input in each case with the additional chilled-water input in Case B; do not assume a combined, weighted PUE numerator is all purchased electricity.
Conclusion
PUE is the ratio of total facility energy to IT energy over a matched boundary and period. For an all-electric facility, multiplying IT electricity by PUE gives total facility electricity; subtracting IT electricity then reveals supporting electricity. Onsite WUE still uses IT electricity as its denominator, while an electricity-related water estimate must account for the electricity serving the whole facility. If a PUE includes non-electric energy inputs, check the electricity meter or energy breakdown before using it for that purpose.
The next lesson will pair the appropriate facility electricity with a geographically and temporally specified water-consumption factor, then combine electricity-related and onsite consumption without double counting.