The previous lesson established that an all-electric facility’s total facility electricity, not just its IT electricity, is the starting point for electricity-related water accounting. This lesson adds a grid water-consumption factor to that electricity and combines the result with onsite consumption. The aim is a defensible total: the same reporting period throughout, compatible units, and no mixing of withdrawals with consumption. Allow about 40 minutes, including the readings.
Two places where water can be consumed
A data center may consume water onsite, for example when cooling water evaporates. Electricity generation may consume water offsite, for example at power plants serving the grid. Both can be attributed to the facility’s operation, but they are distinct physical water flows. Electricity used by a cooling pump can therefore be associated with both onsite evaporation and water consumed to generate the pump’s electricity. Counting those two different losses is not double counting.
The diagram separates onsite cooling water from water associated with electricity generation. Treat it as a boundary sketch, not as a numerical formula: the amount assigned to each part still depends on what was measured and how the grid factor was defined.

The following guidance provides the accounting method. Its crucial distinction is between a withdrawal factor, which counts water taken from a source, and a consumption factor, which counts water not returned to that source.
WP_Guidance-for-Calculating-Water-Use-Embedded.pdf
Read this WRI and WSP guidance for its definitions and its method of multiplying metered electricity by a grid water-use factor.
In “Accounting Methods” (p. 7), begin with the sentence about the objective of embedded water-use accounting. Read the accounting definitions, ending where the authors explain that grid factors have a defined geography and time. Then, under “Calculations” (pp. 8–9), read Steps 1–4, from the instruction to identify purchased electricity through the multiplication rule. Include the two displayed equations immediately after that rule. Notice that the withdrawal and consumption calculations use different factors, even when the electricity quantity is identical.
For this lesson, combined consumption means onsite water consumption plus an estimate of water consumed during generation of the facility’s purchased grid electricity. It is not a claim that all this water was consumed in the data center’s local basin. Nor does a generation-only grid factor automatically include water used to extract fuels or manufacture equipment.
Match the factor to the electricity
For one grid region and one reporting period, the basic calculation is:
where is purchased electricity in kWh and is grid-generation water consumption per kWh of purchased electricity. If the factor is in liters per kWh, the kWh cancel and is in liters.
Before multiplying, check four features of the factor:
- Kind of water flow: consumption, not withdrawal.
- Geography: the grid region assigned to the electricity purchase, rather than an unrelated national figure.
- Time: a factor suitable for the electricity’s reporting period; a historical factor is not automatically a current one.
- Electricity basis: whether the factor is intended to be applied to purchased or delivered kWh, or instead to kWh generated at a plant. Do not silently treat those as interchangeable.
The guidance’s appendix shows why selecting the right column matters as much as selecting the right region.
WP_Guidance-for-Calculating-Water-Use-Embedded.pdf
Return to the WRI and WSP guidance to see regional withdrawal and consumption factors side by side.
In “Appendix 1. U.S. Subnational Grid-Average Water Use Factors (gal/kWh)” (p. 16), read the regional table, focusing on the ERCT row and its separate withdrawal and consumption columns. Read the conversion note immediately below the table as well. The source is cited as thinkstep AG 2018a; do not assume these historical factors describe an unspecified present-day year.
In that historical table, ERCT has a consumption factor of U.S. gallons/kWh, versus a withdrawal factor of U.S. gallons/kWh. Converting the consumption factor with the appendix’s liters per U.S. gallon gives approximately liters/kWh. Multiplying onsite consumption by the gallons/kWh withdrawal figure and calling their sum “total consumption” would change the meaning of the total. The table also shows why a factor needs a source date: its values cannot simply be assigned to a different year.
A combined annual calculation
Return to the illustrative all-electric facility from the previous lesson. Its annual IT electricity is kWh and its PUE is , so total facility electricity is kWh. For this example, assume all of that facility electricity was purchased from the grid; there is no onsite generation or purchased chilled water.
Now add the following hypothetical, matched-year data. These numbers illustrate the method; they are not estimates for a real facility or grid:
- Reporting period: calendar year 2024.
- Onsite water consumption during that year: liters, measured under the stated site boundary.
- Assigned grid: hypothetical Region A.
- Region A’s 2024 grid-generation consumption factor, defined per delivered kWh of purchased electricity: liters/kWh.
First calculate the electricity-related volume:
Then add the separately measured onsite consumption:
The defensible description is: an estimated 19.5 million liters of combined onsite and grid-generation water consumption attributed to this facility in 2024, using the specified Region A average factor. Of that total, 1.5 million liters is onsite; 18 million liters is electricity-related and may be consumed at generation sites elsewhere.
There are two easy ways to inflate or understate this result. Multiplying only the IT kWh by the grid factor omits electricity used by cooling and other supporting equipment. Conversely, multiplying all facility kWh and then adding the supporting electricity again counts that electricity twice. The onsite water volume is added once because it is a different flow, not because cooling electricity was omitted.
If a source-based WUE is wanted as a separate, per-IT-kWh presentation, the same combined volume can be divided by IT electricity:
That division changes the denominator and units of presentation, not the water-accounting boundary or the 19.5-million-liter total.
When one annual grid factor is not enough
A single annual factor is useful when it is appropriate for the facility’s grid and period. If matched factors are available for shorter periods, calculate each period separately and add the volumes:
For example, as an alternative to the liters/kWh scenario above, suppose the same annual kWh comprises kWh in one part of the year at liters/kWh and kWh in the other at liters/kWh. Electricity-related consumption would be liters. With the same liters onsite, the alternative combined estimate is 20.7 million liters. Do not add either period’s result to an estimate already calculated with an annual factor for the same electricity.
Finally, retain the electricity boundary established in the previous lesson. If facility energy includes purchased chilled water, fuel, or onsite generation, PUE times IT electricity is not automatically the purchased grid-electricity quantity. Obtain that quantity separately, and check whether water associated with other energy inputs is included in either the onsite record or any additional estimate before combining them.
Conclusion
To calculate combined consumption, use onsite consumption and multiply the facility’s purchased grid electricity by a geographically and temporally appropriate consumption factor. Keep the periods, kWh basis, and volume units aligned. Add each distinct water flow once; never substitute a withdrawal factor into a consumption total.
This combined figure is useful, but it does not reveal where water pressure occurs. The next lesson examines basin stress, seasonal demand, sources, and return flows to assess what a facility’s water use may mean locally.