Hello. In the previous lesson, you separated a water claim’s activities, water measure, location, period, and denominator. Now you can use those labels to calculate a specific ratio: onsite water usage effectiveness (WUE) in liters of onsite water consumption per kilowatt-hour of IT electricity. The calculation is short; deciding which measurements belong in it takes more care. Allow about 40 minutes for this lesson and its two short readings.
Give both halves of WUE a precise meaning
The site-based WUE formula uses annual site water usage divided by annual IT equipment electricity use. The Department of Energy presents it alongside power usage effectiveness (PUE), which has a different numerator and purpose.
Cooling Water Efficiency Opportunities for Federal Data Centers | Department of Energy
Read the Department of Energy's definitions to see why WUE uses IT electricity even though cooling equipment also consumes electricity.
Under “Low-Cost/No-Cost Water-Saving Opportunities at Existing Data Centers,” just after Figure 1, begin with the paragraph about equipment operating continuously. Read the two metrics and the WUE equation immediately below that passage. Notice that PUE compares two electricity quantities, while WUE compares a water quantity with IT electricity.
For the consumption-based onsite calculation in this lesson, define:
The result has units of liters per kilowatt-hour of IT electricity, or . IT electricity is the energy used by computing, storage, and networking equipment. It is not the electricity used by the entire facility, which also includes supporting systems such as cooling and power distribution.
“Annual” is the usual reporting convention, but the division works for another stated period if the water and IT-electricity measurements cover exactly the same period and site boundary. A power rating in kilowatts is not yet an energy denominator in kilowatt-hours; it must be paired with operating time or replaced by measured electricity use.
The diagram below helps make the water numerator concrete.

In that diagram, the water circulating repeatedly is not a fresh withdrawal on every pass. Evaporated water leaves as vapor and must be replaced. Blowdown is drained from the tower and also requires replacement, but the diagram shows it being treated and returned. Water needed as makeup is therefore not necessarily the same volume as water consumed within a stated boundary.
Check what a published “water use” numerator includes
The Green Grid defines site-based WUE using onsite operational water use and IT equipment energy. Its detailed discussion includes humidification and cooling-system flows; it also lists cooling-tower blowdown among operational water use. That makes the reporting definition important: a figure labeled “WUE” cannot safely be assumed to use only net water consumption.
[PDF] WATER USAGE EFFECTIVENESS (WUE™) - The Green Grid
Read The Green Grid's operational definitions to identify the electricity denominator and the water activities a reported WUE may include.
In Section III, “Water Usage Effectiveness (WUE),” on printed p. 7, find the paragraph beginning “The IT Equipment Energy.” Read the definitions and lists, stopping just before Section IV, “Appropriate Use of WUE and WUEsource.” Focus on the distinction between IT Equipment Energy and Total Facility Energy, then notice that the annual-water-use list mentions evaporation, blowdown, and drift.
For a strictly consumption-based figure, use the reporting definition of consumption established previously: water withdrawn into the site boundary that is not discharged from it during the period, assuming any relevant changes in storage and other flows have been accounted for. If withdrawal and discharge are the only flows and storage is unchanged:
Evaporation generally contributes to that difference. Blowdown that leaves the site as a measured discharge does not contribute to site-level net consumption under this definition, even though it is part of the tower’s makeup-water requirement. A basin-level assessment needs an additional check: discharge leaving the facility does not prove that it returned to the source basin.
Thus, distinguish a reported metric that includes blowdown in “site water usage” from one whose numerator is explicitly net onsite consumption. Both may be expressed in ; the unit alone does not make their numerators equivalent.
Calculate a consumption-based onsite WUE
Suppose one facility reports the following illustrative annual measurements, all for the same calendar year:
| Measurement | Annual amount |
|---|---|
| Water withdrawn for onsite cooling | |
| Water discharged from the site as blowdown | |
| IT equipment electricity | |
| Total facility electricity |
Assume these are the site’s only water flows, its water storage does not change, and the discharge is measured within the same reporting year. The defined onsite consumption is:
Now divide that consumption, not the withdrawal, by IT electricity, not total facility electricity:
The interpretation is specific: during that year, the facility consumed 0.25 liters onsite for each kilowatt-hour used by its IT equipment. This ratio does not say how much water an individual computation used, where the water originated, or whether the discharge returned to the source basin.
Two nearby calculations reveal why labeling matters:
is a withdrawal-based ratio, not the consumption-based WUE calculated above. Meanwhile,
uses the wrong electricity denominator for WUE. Its smaller number does not demonstrate improved water performance; it results from dividing the same water volume by a larger electricity quantity. All three results have dimensions of liters per kilowatt-hour, but they answer different questions.
Read the result within its boundary
An onsite WUE is useful for describing water intensity relative to IT electricity. It does not measure total annual water consumption by itself: a facility can lower its liters-per-IT-kilowatt-hour ratio while its overall IT electricity use, and potentially its total water consumption, grows. Nor does an onsite WUE include water consumed offsite to generate purchased electricity.
The immediate discipline is to attach a complete label to the answer:
of onsite water consumption per IT-equipment kilowatt-hour, for this facility and calendar year, excluding electricity-related offsite water consumption.
If the source instead reports “annual site water usage” without defining how returned blowdown is treated, preserve that wording and flag the uncertainty. Do not quietly substitute a withdrawal figure for consumption, or assume a discharged volume returned to the source basin.
Conclusion
To calculate consumption-based onsite WUE, establish onsite consumption in liters, establish IT equipment electricity in kilowatt-hours for the same site and period, then divide. Recirculated flow is not repeatedly counted as new water; withdrawal, discharge, and consumption remain distinct. Published WUE figures require a numerator-definition check, especially when blowdown is included in reported “water usage.”
The next lesson turns to total facility electricity and PUE. That electricity quantity is deliberately not today’s WUE denominator, but it will matter when accounting for water associated with electricity generation.