Hello! Welcome back to your course on UK electrical grids.
In our last lesson, we established that the growth of Distributed Generation (DG) is transforming our traditionally one-way distribution networks into two-way systems, causing reverse power flow and voltage rise. We concluded by asking what this means for the network's safety systems, which were built for a simpler, one-way world.
Today, we answer that question directly. The learning outcome for this lesson is to describe the impact of distributed generation on network protection schemes, fault levels, and system safety.
We will investigate three main areas:
- How DG changes the magnitude and direction of fault currents.
- The main ways DG can cause protection systems to malfunction, such as "blinding" and "false tripping".
- The critical safety issues DG introduces, including "unwanted islanding" and interference with automated fault-clearing systems.
1. A Fundamental Shift: From One-Way to Two-Way Faults
As we've learned, traditional distribution networks are radial, with power and fault currents flowing in one direction: from the substation outwards. Protection systems, like overcurrent relays, are designed with this simple logic. They are set to detect abnormally high currents and are coordinated based on the assumption that the fault is always "downstream".
Distributed Generation breaks this fundamental assumption. When a fault occurs on a network with DG, the fault is now fed with current from two directions:
- From the main grid via the substation.
- From the local DG unit(s).
This turns a simple radial network into a more complex, multi-source system during a fault. To begin, let's explore this concept and its first major consequence: the change in fault level.
Impact of Distributed Generation on the Protection ...
This article, 'Impact of Distributed Generation on the Protection of Distribution Networks', introduces how DG changes the basic operation of distribution networks, making them more complex to protect.
Please read the introductory section titled 'THE IMPACT OF DISTRIBUTED GENERATION'. It sets the scene by explaining how DG moves distribution networks away from simple radial operation.
Changing Fault Levels
The fault level (or short-circuit level) is the maximum current that would flow at a specific point on the network during a fault. The circuit breakers and protection relays are all sized and configured based on the expected fault level.
By providing an additional source of current during a fault, DG typically increases the fault level. This can exceed the design ratings of network equipment, but more importantly, it disrupts the careful calculations used to coordinate protection.
The following resource provides a concrete example of this increase.
Impacts of Distributed Generation on Power System ...
This research paper, 'Impacts of Distributed Generation on Power System Protection', includes a case study that clearly demonstrates the effect of DG on fault levels.
Please read the short subsection 'A. DG Impacts on Fault Level' within the 'Case Study' section. Focus on TABLE II, which shows a clear percentage increase in fault current when a DG unit is connected.
As you saw in the table, the presence of DG increased the fault current by over 20%. However, the type of DG also matters. A traditional synchronous generator (like a large diesel engine) will contribute a very high fault current. In contrast, modern solar and wind farms are connected via inverters, which are power electronic devices. Their fault current contribution is limited by their internal software and hardware, creating a different set of challenges for protection engineers.
To understand this crucial difference, the following video explains what "inverter-based resources" are.
Connecting Solar to the Grid is Harder Than You Think
This video from Practical Engineering explains why solar, wind, and batteries are fundamentally different from traditional power plants.
Please watch the section from 02:38 to 04:31. This will clarify why most renewable DG is considered 'inverter-based' and doesn't behave like the spinning generators of old.
This multi-directional and altered flow of fault current leads to several specific problems with protection schemes.
2. Malfunctioning Protection: Blinding and False Trips
The changes in fault current can cause protection devices to misinterpret what is happening on the network, leading to two classic problems: blinding and false tripping.
The following reading provides an excellent overview of the potential problems DG can cause.
Impact of Distributed Generation on the Protection ...
Let's return to the 'Impact of Distributed Generation on the Protection...' article. It lists the most common protection problems caused by DG.
Please read the section 'POTENTIAL PROBLEMS TO PROTECTION'. This will give you a checklist of the issues we are about to explore in more detail.
Now, let's dive into the two most significant issues from that list.
A. Blinding of Protection
Protection "blinding" occurs when a relay fails to see a fault that it should have detected.
Imagine a fault occurs far down a feeder. The DG unit, being closer to the fault, starts feeding a large current into it. From the perspective of the main substation relay, the current it needs to supply is now reduced because the DG is helping to "feed the fault". If this reduction is large enough, the current seen by the substation relay may fall below its trip setting. The relay is "blinded" to the fault, which remains on the system, posing a safety risk and potentially damaging equipment.
Impact of Distributed Generation on the Protection ...
This section of the article explains the concept of blinding in detail, complete with a helpful diagram.
Please read the section 'THE BLINDING OF PROTECTION - PREVENTING OVERCURRENT RELAY OPERATION'. Pay close attention to Figure 1, which illustrates how the generator's current (I2) reduces the current seen by the grid's protection relay (I1).
B. False Tripping (Sympathetic Tripping)
False tripping is the opposite problem: a protection device on a healthy part of the network operates incorrectly.
Imagine a fault on Feeder 1. A large DG unit on an adjacent, healthy Feeder 2 sees this fault (as a voltage dip) and begins exporting a large fault current back towards the substation to feed the fault on Feeder 1. The protection relay on the healthy Feeder 2 sees this large outward current and mistakenly concludes there is a fault on its own feeder. It then trips, unnecessarily cutting off power to all customers on the healthy Feeder 2.
Impact of Distributed Generation on the Protection ...
The next section in the same article explains this phenomenon of sympathetic tripping.
Please read the section 'FALSE TRIPPINGS'. Figure 4 clearly shows how a fault on one feeder can cause a DG on another feeder to trigger a trip.
To solve these issues, DNOs often need to upgrade protection to more advanced "directional" relays, which can determine the direction of the fault current, making them smart enough not to be fooled by DG.
3. Critical System Safety Impacts
Beyond confusing the logic of relays, DG can compromise fundamental safety mechanisms of the grid.
A. Unwanted Islanding
If a fault or maintenance action causes the main grid supply to a feeder to be disconnected, any DG on that feeder should also disconnect immediately. If it doesn't, it will continue to energise that section of the network, creating an island.
This is extremely dangerous for several reasons:
- Safety of Personnel: Utility workers may believe the line is de-energised and begin work on it, risking electrocution.
- Power Quality: The DG unit may not be able to maintain stable voltage and frequency within the island, potentially damaging customer equipment.
- Reconnection Damage: If the main grid supply is reconnected while the island is still running, the two systems will be out of synchronisation. This can cause massive current surges, destroying the generator and other network equipment.
For these reasons, all DG must have robust anti-islanding protection.
Impact of Distributed Generation on the Protection ...
This section explains the dangers of islanding and why anti-islanding protection is a mandatory safety feature.
Please read the section 'ANTI-ISLANDING PROTECTION'. Focus on the three bullet points that list the reasons why islanding is undesirable.
B. Interference with Auto-Reclosing
On overhead line networks, around 80% of faults are temporary (e.g., a lightning strike or a tree branch briefly touching the line). To improve reliability, networks use auto-reclosers—devices that automatically trip the line and then re-close it after a fraction of a second. This brief "dead time" is usually enough for the temporary fault arc to extinguish.
However, if a DG unit is present on the line, it can continue to feed current into the fault during the dead time. This prevents the arc from extinguishing, effectively turning a temporary, self-clearing fault into a permanent one that requires manual intervention.
Impact of Distributed Generation on the Protection ...
The final section from this article discusses how DG can defeat the purpose of auto-reclosers, a key tool for maintaining grid reliability.
Please read the section 'AUTORECLOSING' to understand this final, crucial impact on protection and safety.
Conclusion
In this lesson, we've seen that integrating Distributed Generation into a grid designed for one-way power flow has profound consequences for its protection systems and overall safety.
Here are the key takeaways:
- DG changes the grid from a single-source radial network to a multi-source network during faults, altering the magnitude and direction of fault currents.
- This can cause protection schemes to fail in two main ways: protection blinding (failing to detect a real fault) and false tripping (disconnecting a healthy part of the network).
- DG introduces significant safety risks, such as creating dangerous unwanted islands of power and preventing auto-reclosers from clearing temporary faults.
- These challenges mean that connecting DG often requires significant and costly upgrades to the protection system, moving from simple overcurrent relays to more intelligent, directional schemes.
In our last lesson, we saw how DG can cause voltage rise. In this lesson, we've seen how it impacts protection. There is one more major constraint: the physical capacity of the wires and transformers themselves. Just like a pipe can only carry so much water, a cable can only carry so much current before it overheats.
In our next lesson, we will explore this issue: explaining how distributed generation connections can exceed the thermal capacity of network assets like cables and transformers.