Calculating Cooling-Tower Makeup Water Using a Steady-State Water Balance

This lesson is built with resources from youtube.com, epa.gov and 1 more site.

Welcome back. The previous lesson distinguished a facility’s withdrawal from its discharge and showed why recirculating water is not withdrawn again on every pass. This lesson brings those ideas inside a cooling tower: you will calculate the makeup water needed to replace evaporation, blowdown, and drift while keeping circulation out of the supply total. Estimated study time: 35–40 minutes.


Put a boundary around the circulating loop

A cooling tower repeatedly sends water through equipment that has absorbed heat, then cools that water for another pass. The circulating flow can be large, but most of it remains within the loop. Makeup water is the new water added to replace what leaves.

Watch this short demonstration before following the balance. Notice the difference between water pumped around the loop and water entering from the replacement supply.

Cooling Tower Basic Operation

Watch “Cooling Tower Basic Operation” from Chem-Aqua for a visual account of circulation, evaporation, and replacement water.

Watch the circulating loop to see water pass through a heat exchanger and tower. Continue with the replacement supply, focusing on why evaporation and the deliberate discharge of mineral-rich water lower the reservoir level.

The demonstration highlights two losses. A third, drift, consists of liquid droplets carried out with the tower’s exhaust air. Unlike evaporation, drift remains liquid as it leaves the equipment. The U.S. Environmental Protection Agency’s WaterSense at Work section on cooling towers sets out all three flows and its makeup-water equation.

6.3 Cooling Towers

Read the U.S. Environmental Protection Agency’s explanation to connect the physical losses with the water-balance equation.

In Section 6.3, read the “Evaporation,” “Blowdown or Bleed-Off,” and “Drift” subsections on p. 6-9, from the tower losses. Then, on p. 6-10, read “Leaks or Overflows” and “Equation 6-3. Cooling Tower Make-Up Water,” from the makeup equation. Focus on which flows leave the system; the later discussion of cycles of concentration is not needed for this calculation.

Evaporation removes water as vapor while leaving most dissolved minerals in the liquid. Blowdown deliberately drains some of that increasingly mineral-rich liquid. Drift carries away small liquid droplets. Each reduces the amount of water in the loop, so each must be replaced to maintain its level.



Derive the steady-state balance

Choose a boundary that encloses the whole circulating loop, including the tower and its reservoir. Water pumped around that loop stays inside the boundary. With no leaks or other additions and losses, makeup is the incoming flow; evaporation, blowdown, and drift are the outgoing flows.

If the amount of water stored in the loop remains steady, incoming water must equal outgoing water:

Here is makeup, evaporation, blowdown, and drift. All four must use the same kind of unit and reporting period—for example, liters per hour throughout, or cubic meters over one day throughout.

The steady-state assumption matters. During a tank refill, makeup may temporarily exceed the losses because stored water is increasing. During a drawdown, it may fall short. If there is a measured leak , include it as another outflow:

Do not add the circulating flow to either result. It measures how much water passes through part of the equipment, not how much new water crosses into the complete loop. A loop can circulate the same water many times while requiring only enough makeup to replace its losses.



Close the balance in a diagram

Steady-state cooling-tower example showing makeup entering and evaporation, controlled blowdown, and drift leaving. The lower panels show separate water-volume and dissolved-constituent balances.

The diagram gives evaporation as cubic meters per hour, blowdown as cubic meters per hour, and drift as cubic meters per hour. Their sum determines the required makeup:

That is liters per hour. If those rates hold continuously for 24 hours, makeup over the day is:

The conversion changes the reporting period, not the underlying water use. It would be incorrect to label cubic meters per hour as cubic meters per day.

The diagram also displays concentrations and a constituent balance. Those values describe dissolved material, not additional water flows to add to . Its “five cycles of concentration” refers to how concentrated the circulating water’s constituents are relative to makeup water; it does not mean that water makes only five trips around the loop.

For a second scale check, suppose a tower circulates 9,000 liters per minute, evaporates 180 liters per minute, drains 35 liters per minute as blowdown, and loses 2 liters per minute as drift. Its makeup requirement is:

The 9,000-liter-per-minute circulation rate is neither a fourth loss nor a new supply rate. It describes repeated movement of water already in the system.



Say what the makeup number does—and does not—measure

Makeup is a supply requirement at the cooling-loop boundary. If a facility pumps it directly from a river, that pump rate can represent a direct withdrawal from the river. If a utility delivers it, the facility has a delivery, while the source withdrawal must be traced to the utility. The balance alone does not identify the source.

Nor does makeup automatically equal consumption. In the diagram, cubic meters per hour leave as vapor; leave as blowdown liquid; and leave as drift droplets. Blowdown is a discharge from the equipment, but whether it returns to the source basin depends on its subsequent route. Drift, too, should not be silently relabeled evaporation. The previous lesson’s source-basin and destination questions still apply after the equipment balance is complete.

A useful check on any reported cooling-tower number is therefore to keep two statements separate: how much replacement water entered the loop, and where each loss went. The first follows from the steady-state equation; the second requires information beyond it.



Key takeaways

At steady state, makeup equals evaporation plus blowdown plus drift, with any other known losses added explicitly. Use consistent units and periods, and never count water circulating inside the loop as a fresh withdrawal on each pass. The resulting makeup figure describes replacement supply—not, by itself, evaporation, consumption, or a source-basin impact.