Hello. Last lesson traced heat from IT equipment through air or liquid circuits to the outdoors, and distinguished circulating water from water that leaves a system as vapor. This lesson puts a quantity on that vapor loss. Given a heat load, the share of heat rejected by evaporation, and a latent heat of vaporization, you will be able to estimate how much water evaporates over a stated period.
Allow about 35–40 minutes, including a short video, a focused reading, and time to follow the calculations.
Why evaporation removes heat
When liquid water becomes vapor, it absorbs energy. That energy is called the latent heat of vaporization. In an evaporative cooler or cooling tower, some water takes up heat and leaves with the air as vapor. The rest of the water can remain in the circuit and make another trip.
Watch the opening of Latent Heat of Fusion and Vaporization, Specific Heat Capacity & Calorimetry from The Organic Chemistry Tutor. It introduces the distinction needed here: energy that changes water’s temperature is not the same as energy that changes its phase.
Latent Heat of Fusion and Vaporization, Specific Heat Capacity & Calorimetry - Physics
Watch the opening explanation of latent heat and the energy required for a phase change.
Watch latent heat. Focus on the relationship between an amount of energy, a mass of water, and the energy required to vaporize each unit of mass. The video also discusses melting; for this lesson, concentrate on vaporization.
The schematic below shows where that phase change fits into a cooling loop. Warm water is sprayed into upward-moving air. Some evaporates; water collected at the bottom is pumped around again. The diagram separately labels drift—liquid droplets carried out by air—and blowdown—water deliberately drained from the circuit. Neither is the vapor loss calculated in this lesson.

Convert heat into evaporated mass
Suppose the supplied heat load is , the fraction of that heat rejected through evaporation is , and the supplied latent heat of vaporization is . The evaporative share of the heat load must equal the rate at which evaporating water absorbs energy. Rearranging gives:
Here, is the mass evaporated per unit time. The units provide a useful check. If the heat load is in kilowatts, it supplies kilojoules per second; if latent heat is in kilojoules per kilogram, the result is kilograms per second:
The fraction refers to heat, not to the fraction of circulating water that evaporates. For instance, means evaporation rejects 60% of the stated heat load. Other heat-transfer processes reject the remainder. A dry heat-rejection process has for this estimate; assuming means assigning the entire stated load to evaporation. Neither value should be assumed for an actual installation without a reason.
For an illustrative latent heat of , a steady thermal load rejected entirely through evaporation gives:
Multiplying by seconds per hour gives approximately . Using about for liquid water, that is , or about US gallons per hour. If only half the same load is rejected through evaporation, the estimated evaporated volume is half as large.
The value is an illustrative supplied value, not a universal constant for every operating condition. In a claim comparison, use the latent heat specified for the estimate—or state the value you assumed.
Read a data-center example critically
The following example from Lawrence Berkeley National Laboratory applies the same physical idea to a data-center heat load. Its purpose here is to connect the calculation to operating equipment, not to establish one water-use rate for all facilities.
[PDF] Humidity Control in Data Centers
Read the Lawrence Berkeley National Laboratory example to see how a heat load becomes an estimated evaporation rate, and why a chiller can change the heat that must be rejected.
In the PDF's “To Provide Free Cooling” discussion, find item 3 and then Scenario 1, beginning with the paragraph about avoiding direct evaporative cooling. Read the comparison through its note about blowdown. It begins on p. 16 and continues onto p. 17. Focus on the stated 1 MW heat load, the 970 Btu per pound latent heat, and the additional heat attributed to running the chiller; set aside the broader cooling-design argument for now.
The reading uses , approximately , rather than the illustrative used above. Dividing the same heat load by this smaller latent-heat value yields roughly , or about US gallons per hour—close to the reading’s estimate. Different stated latent-heat assumptions produce different numerical answers without changing the method.
Also notice which heat load is being estimated. The reading’s example contrasts rejecting a load with rejecting that load plus heat added by operating a chiller. If supplied data say the outdoor unit rejects , putting into the formula would omit part of its load. Conversely, adding chiller heat to a supplied load that already includes it would count that heat twice. Use the load defined at the heat-rejection boundary.
Estimate consumption over a reporting period
A rate becomes a volume only after you specify a duration. Suppose an outdoor system rejects a steady thermal load for eight hours, with 60% of that heat rejected through evaporation. Use a supplied latent heat of .
First calculate the evaporation rate:
That is , approximately . Over eight hours, the estimate is:
This is evaporated water over eight hours, not on every pass through the loop. It is also not automatically the total makeup-water requirement: drift, blowdown, and other losses can require additional replacement water, as the reading notes.
For a varying load or operating mode, divide the reporting period into intervals with appropriate loads and evaporative fractions, calculate each interval’s evaporation, and add the results. An annual estimate based on one hot-hour rate would otherwise imply that the same conditions persisted all year.
Key takeaways
To estimate evaporation, identify the heat load at the boundary being cooled, multiply by the fraction of that heat rejected through evaporation, and divide by the supplied latent heat of vaporization. Check the units, then multiply the resulting rate by the operating time. Approximately one kilogram of evaporated water corresponds to one liter of liquid water.
The result describes vapor loss, not circulating flow or necessarily all onsite water use. The next lesson uses supplied temperature, electricity-demand, and water-demand data to compare dry, evaporative, and hybrid cooling choices.