Hello! Welcome to your sixth lesson in the UK electrical grids course.
Introduction
In the last lesson, we established the fundamentals of three-phase systems. You learned to describe star (wye) and delta connections and, crucially, to distinguish between phase and line quantities, understanding the relationship that connects them.
- Recap: Star Connection: and
- Recap: Delta Connection: and
Today, we will use this foundation to perform one of the most common tasks in power system analysis: calculating power.
Learning Outcome: By the end of this lesson, you will be able to calculate real power (), reactive power (), and apparent power () in balanced three-phase loads.
We will cover:
- How to determine total power from the power of a single phase.
- The standard formulas for calculating three-phase power using line voltage and line current.
- Step-by-step examples for both star and delta connected loads.
For this lesson, we will focus on balanced systems, where the load impedance is identical for all three phases. This is a very common and practical assumption for analysing large motors or entire substations.
1. From Single-Phase to Three-Phase Power
Remember the power triangle from our lessons on single-phase circuits? The same concepts of real power (), reactive power (), and apparent power () apply to each phase of a three-phase system.
In a balanced system, each of the three phases has an identical load. This means each phase draws the same amount of real power and the same amount of reactive power. Therefore, the simplest way to find the total power is to calculate it for one phase and multiply by three.
Apparent Power in a Three Phase Balanced WYE Circuit
This video explains this fundamental principle. It shows how the power triangles for each of the three balanced phases are identical and can be simply added together to find the total power.
Watch from 00:56 to 03:39. Focus on the idea that for a balanced load, total power is simply three times the power of any single phase.
2. The Universal Three-Phase Power Formulas
While calculating power on a per-phase basis is always correct, it's often more convenient to work directly with line quantities ( and ). These are the values most commonly specified for equipment and measured in the field (e.g., a "400V, three-phase motor" refers to the line voltage).
Through a mathematical derivation, we can create a set of formulas that use line quantities. A key insight is that these formulas are the same for both star and delta connections.
Apparent Power in a Three Phase Balanced WYE Circuit
The same video continues to derive the standard formula for apparent power using line quantities. It shows how the per-phase formula is converted using the star connection voltage and current relationships.
Watch from 03:39 to 06:58. Follow the steps as the presenter transforms the equation S_total = 3 * V_phase * I_phase into the final line quantity formula. Note how the same logic is then applied to find real and reactive power.
The resulting formulas are fundamental to all three-phase power calculations:
- Apparent Power (S): (in VA)
- Real Power (P): (in W)
- Reactive Power (Q): (in VAR)
Here, is the phase angle of the load impedance, and is the power factor.

For a detailed text summary of these formulas and how they apply to both star and delta connections, you can refer to the following resource.
This webpage from Omni Calculator provides a concise written explanation of the power formulas.
Read the sections titled 'What is apparent power...', 'What is active or real power?', 'What is reactive power?', and 'What is the difference between power consumption in star and delta connections?'. This will reinforce the formulas and the fact that they apply to both connection types.
3. Calculation Walkthrough
Let's apply these formulas. The process usually involves two main stages:
- Determine the phase and line voltages and currents.
- Use these values to calculate the total power.
First, let's refresh our understanding of voltage and current calculations with some worked examples.
3 Phase: How to Calculate Line Voltage, Phase Voltage, Line Current & Phase Current in Star & Delta
This video from Joe Robinson Training provides clear, step-by-step calculations for finding voltages and currents in star and delta circuits. We will use the values from these examples to calculate power.
First, watch the star connection example from 00:26 to 06:31. Then, watch the delta connection example from 06:31 to 12:15. Pay close attention to the values calculated for Vp, Ip, and IL in each case.
Now, let's extend those examples to calculate power.
Example 1: Star-Connected Resistive Load
From the first video example, we have a star-connected load with:
- Line Voltage (): 415 V
- Load Resistance per phase: 25
- Calculated Line Current (): 9.58 A
Since the load is purely resistive, the power factor is 1 () and the phase angle is 0°.
-
Calculate Total Apparent Power ():
-
Calculate Total Real Power ():
-
Calculate Total Reactive Power ():
As expected for a resistive load, there is no reactive power.
Example 2: Delta-Connected Resistive Load
From the second video example, the same 25 resistors are now in a delta connection:
- Line Voltage (): 415 V
- Calculated Line Current (): 28.75 A
- Power Factor: 1
-
Calculate Total Apparent Power ():
-
Calculate Total Real Power ():
-
Calculate Total Reactive Power ():
Notice that connecting the same loads in delta draws three times more power than in star (). This is because in delta, each resistor has the full line voltage across it, whereas in star it only has the phase voltage ().
Example 3: Star-Connected Inductive Load (Motor)
Let's take a more realistic example of a three-phase motor connected in star to a 400V supply. Each phase winding has an impedance of .
-
Find Impedance Magnitude and Power Factor:
- Magnitude:
- Phase Angle:
- Power Factor: lagging (since the reactive part 'j6' is positive, it's an inductive load).
-
Find Voltages and Currents:
- The supply is 400V, so .
- It's a star connection, so phase voltage is .
- Phase current is .
- For a star connection, line current equals phase current: .
-
Calculate Total Powers:
- Apparent Power:
- Real Power:
- Reactive Power:
- Apparent Power:
This final example represents a complete calculation for a typical three-phase load.
Conclusion
Key Takeaways:
- In a balanced three-phase system, the total power () is three times the power of a single phase.
- A single set of formulas using line quantities can be used to calculate power for both balanced star and delta connected loads.
- The key formulas are:
- Calculating three-phase power is a two-step process: first find the line voltage and current, then apply the power formulas.
Next Lesson Preview
We have now covered the fundamentals of three-phase systems, from their structure to power calculations. In the next lesson, we will step back and look at the bigger picture, discussing the practical and economic advantages of using three-phase power transmission over single-phase systems for the national grid. The concepts of power and current you've learned today will be key to understanding why.